Modbus TCP
Set up the Modbus TCP protocol for ENLYZE.
This guide walks you through connecting data sources that communicate via Modbus TCP. Modbus is an open, vendor-neutral protocol supported by many devices on the machine network, such as energy meters, temperature controllers, frequency inverters, sensors, and PLCs. ENLYZE connects these devices over Ethernet via Modbus TCP (default port 502). In the ENLYZE Platform, the connector is called Modbus TCP.
Supported devices
You can connect any device that works as a Modbus TCP server (slave), including:
energy meters and power analyzers, e.g. from Janitza
temperature controllers, frequency inverters, and sensors with an Ethernet interface
PLCs with a Modbus TCP server function, e.g. Siemens LOGO! 8
You connect devices that only speak Modbus RTU (serial, RS-485) through a Modbus gateway (TCP to RTU). In the ENLYZE Platform, you then create the gateway as a Modbus TCP data source and address the individual devices through their unit ID. If you want to connect an RTU device directly to the serial interface of the Edge Device, contact us at support@enlyze.com.
Before you start
Have the following ready:
the IP address of the device or of the Modbus gateway
the device's register map, usually found in the manual or provided by the machine builder. For each value it lists the register type, the address, the data type and, for values spanning several registers, the word order (see Addresses and data types)
the device's unit ID, if the register map does not state it
Connect the data source to the network
If not done yet, first establish a network connection between the data source and the respective Edge Device. You can find the possible networking scenarios here. The connector opens a TCP connection to the device on port 502. If there is a firewall, make sure this port is open between the Edge Device and the device.
Use the network tools to ping the device and check that it is reachable from the Edge Device.
Create the data source
Open the ENLYZE Manufacturing Data Platform, select the machine you want to add this data source to, and click + Data source.
Enter a descriptive name and add the manufacturer and model of the device under Device details, e.g. Janitza and UMG 604.
Add connection details
Under Connection details, select the Edge device. You can find its name on the sticker on the device (format adjective-scientist). Select Modbus TCP as the Connector and fill in the connector details:
IP address: the IPv4 address of the device or of the Modbus gateway
Port: the default is
502. Only change it if the device answers on a different port.Ephemeral connections: when enabled (the default), the Edge Device opens a new connection to the device for every readout. When disabled, it keeps one connection open permanently. Keep the default unless we recommend otherwise.
You don't enter the unit ID here. You set it for each variable instead.
Click Save and confirm with Save and try to connect. The Edge Device connects to the device.
Add variables
Open the Variables tab on the data source page. As long as the data source has no variables, it offers two ways: Add manually and Add via MCP Server.
You need the device's register map.
Click Add manually. The Add variables dialog opens.
Fill in one row per variable. Addresses and data types explains what goes into each column:
Register type: Coil, Discrete input, Input register, or Holding register
Slave ID: the device's unit ID (
0to255)Address: the register address, counted from
0(0to65535)Data type: e.g.
UINT16orFLOAT32BE. ForSTRING[n], also enter the String length in bytes.Display name, Unit, and Scaling factor: how the value is shown in the ENLYZE Platform. Unit and scaling factor are only available for numeric values.
State: Evaluating (recommended) records the variable in the Exploration state, so you can check the values before you activate it. Active records it right away and makes it available to all services. An active variable requires a display name.
Use Add row to add more variables. You can add up to 100 rows at a time.
Click Add variables.
If a variable already exists, it is not created twice. The dialog tells you in the affected row.
You need an AI assistant connected to the ENLYZE MCP (see Set up ENLYZE MCP) and information about the device: the data sheet or register map as a PDF, CSV, or link, or alternatively a photo of the type plate.
Click Add via MCP Server.
Click Copy prompt. The prompt already contains the site, machine, and data source.
Paste the prompt into your AI assistant and share the device information.
The assistant reads the register map, converts the addresses, and asks you whenever something is not clearly documented, such as word order, scaling, or unit ID.
Review the proposed variable table and approve it. Only then does the assistant create the variables in the ENLYZE Platform.
Check the values and activate the variables
Variables in the Evaluating state are already recorded but not yet available to all services. Compare the first values with a known value, such as the reading on the device display. If they are clearly off, see Check the values. Once the values are right, contextualize and activate the variables. See all available variables in the Variables tab takes you straight there.
Addresses and data types
Register maps are structured differently from one manufacturer to the next. The following sections show how to transfer the details from the manual into the fields of the ENLYZE Platform.
Register types
Coil
0xxxx
single bit, readable and writable
BOOL
Discrete input
1xxxx
single bit, read-only
BOOL
Input register
3xxxx
16-bit register, read-only
all except BOOL
Holding register
4xxxx
16-bit register, readable and writable
all except BOOL
You can't read a single bit inside an input or holding register directly as BOOL. In that case, add the register as UINT16 and contact us if you want to evaluate the bit separately.
Address
The ENLYZE Platform expects the address that is actually sent over the network. It is counted from 0 and contains no digit for the register type. Many manuals use the classic notation instead, which is counted from 1 and where the first digit indicates the register type. This is how you convert it:
40001
Holding register
0
40101
Holding register
100
30001
Input register
0
10005
Discrete input
4
00010
Coil
9
If the manual already gives the address without a type digit (e.g. "register 100" or 0x0064), it is usually counted from 0 already and you can use it as is. Convert hexadecimal values to decimal: 0x0064 is 100.
Data types
A Modbus register holds 16 bits. Larger values occupy several consecutive registers. The address is always that of the first register.
BOOL
1 bit (coil and discrete input only)
Boolean
INT16, UINT16
1
Integer
INT32BE, INT32LE, UINT32BE, UINT32LE
2
Integer
INT64BE, INT64LE, UINT64BE, UINT64LE
4
Integer
FLOAT32BE, FLOAT32LE
2
Float
FLOAT64BE, FLOAT64LE
4
Float
STRING[n]
n/2
String
INT stands for signed integers, UINT for unsigned ones. For STRING[n], n is the length in bytes and must be an even number.
Word order
For values spanning several registers, the suffix BE or LE defines the order in which the registers are combined:
BE: the first register holds the most significant part of the value. Manuals call this "big endian", "high word first", orABCD. This is the most common order.LE: the first register holds the least significant part of the value. Manuals call this "word swap", "low word first", orCDAB.
The bytes within a register are always read in the Modbus standard order. Devices with swapped bytes (BADC, DCBA) are not supported.
Unit ID
The unit ID (Slave ID in the ENLYZE Platform) defines which device behind an IP address is addressed.
Device directly on the network: many devices ignore the unit ID or expect a fixed value, usually
1or255. The manual tells you the right value.Device behind a Modbus gateway: the unit ID is the bus address set on the RTU device. This lets you connect several devices through one gateway and one data source.
Scaling factor
Many devices transmit measured values as integers with a fixed factor, e.g. 2305 for 230.5 V. You find the factor in the register map. Enter it as the Scaling factor, 0.1 in this example. The scaling factor must not be 0.
Check the values
After adding the variables, check the first values against a known value. Typical deviations and their causes:
Implausibly large or tiny values (e.g.
1.2E-38instead of230.5): the word order is wrong. Switch betweenBEandLE.Values belong to a neighboring measurement: the address is off by one. Check the conversion from the classic notation.
Values off by a factor of 10, 100, or 1000: the scaling factor is missing or wrong.
No values: register type, address, or unit ID don't match the device. Only add addresses the device actually provides. Each variable is read with its own request, and registers that can't be read slow down the readout of the remaining variables.
If you have any questions, feel free to contact us at support@enlyze.com.