If a SPARK is shown as offline in the ENLYZE App or cannot establish a connection during initial integration, the following page will help you quickly identify and resolve the issue.
By default, a SPARK’s network communication is restricted. A SPARK can communicate with other network participants if:
They are in the same network as one of the SPARK’s network interfaces.
They have access to the SPARK’s Internet (eth0) network via a gateway.
To access the SPARK from other networks, a manual route must be configured. Learn how to set up routes .
Please verify the following before starting the troubleshooting process:
If all of the above conditions are met, you can begin the diagnostic process.
Our diagnostics process helps you identify and resolve connection issues step by step.
Access ENLYZE EDGE on the respective SPARK. If you need help, you can find the appropriate guide . The connection test to the ENLYZE Manufacturing Data Platform will start automatically once you’ve successfully logged in and will show where the connection fails. You can run a new connection test at any time by clicking the “Test Connection” button.
The connection tests are sequential, ensuring that troubleshooting starts at the correct step. Fix the first displayed issue and run the test again to confirm the SPARK has reconnected to the ENLYZE Manufacturing Data Platform.
Follow the steps in the process outlined below.
Incorrect firewall settings are the most common cause of connection issues. Ensure the following rules are configured:
1.1.1.1
53 (DNS)
TCP and UDP
Hostname resolution
8.8.4.4
53 (DNS)
TCP and UDP
Hostname resolution
8.8.8.8
53 (DNS)
TCP and UDP
Hostname resolution
iot-edge-1.enlyze.com (159.69.177.150)
51821 (Wireguard)
UDP
Data transfer to ENLYZE Cloud, SPARK configuration, update deployment
ntp1.enlyze.com (157.90.230.207)
123 (NTP)
UDP
System time synchronization
ntp2.enlyze.com (162.55.43.234)
123 (NTP)
UDP
System time synchronization
SPARKs Must Be Exempt from UDP Flood Attack Protection
To ensure smooth communication, it is necessary to whitelist the SPARKs in the UDP Flood Protection module.
If the connection issue cannot be resolved, you’re unsure, or you’re stuck, reach out to us at – we’ll help you quickly and without hassle!