OPC-UA server

Connect an OPC-UA client to the Edge Device's OPC-UA server.

The Edge Device can provide the live values of its data sources through its own OPC-UA server. In this guide you set up the server and connect an OPC-UA client to it, for example UaExpert, a SCADA system or an IIoT platform such as Litmus.

The OPC-UA server runs directly on the Edge Device and is reachable on the local network. It provides the current values of all variables the Edge Device reads, but no history and no production context. For stored time series, production runs or OEE, use the Quickstart.

In the ENLYZE Platform you set up the server as a data sink. A data sink defines where an Edge Device sends its data. Every Edge Device has a data sink for the ENLYZE Platform, which ENLYZE manages.

Prerequisites

  • The Edge Device is online and reads data from at least one data source.

  • The computer running the OPC-UA client can reach the Edge Device on the network.

  • You can edit the Edge Device's data sinks in the ENLYZE Platform.

Set up the OPC-UA server

  1. Open Edge Devices in the sidebar and select the Edge Device.

  2. Open the Data sinks tab and click Add data sink.

  3. Select OPC UA as the Type.

  4. Check the settings (see the table below) and add at least one user.

  5. Click Save.

The Edge Device picks up the configuration automatically and starts the server.

Setting
Default
Meaning

Application name

ENLYZE OPC UA @ <Edge Device>

Name the server shows in the client

Port

4840

TCP port of the server

Minimum transport security

SHA-256 policies or stronger

Weakest security policy the server offers

Require Sign & Encrypt

On

Only allows encrypted connections, no sign-only ones

Minimum password token security

SHA-256 policies or stronger

Weakest security policy a client may use to encrypt the password

Allow anonymous login

Off

Login without username and password

Users

none

Username and password (at least 6 characters) for logging in

An Edge Device has at most one OPC-UA server. The type of a data sink cannot be changed afterwards. To edit or delete the server, use the menu in its row on the Data sinks tab.

ENLYZE stores passwords only as hashes, so a forgotten password cannot be looked up: remove the user and add it again with a new password.

Build the server URL

The server URL has this format:

  1. Open the Edge Device's Overview tab. Network interfaces lists the IP addresses of the Edge Device.

  2. Pick the IP address of the network interface that is on the same network as the OPC-UA client.

  3. The port is in the Port column of the Data sinks tab (default 4840).

Example: the network interface towards the machine has the IP address 192.168.10.25 and the port is 4840. The server URL is opc.tcp://192.168.10.25:4840.

The Edge Device reports these IP addresses itself. While it is offline, the ENLYZE Platform shows the state of its last connection.

Connect the OPC-UA client

Enter the server URL directly

Enter the server URL in the client as the Endpoint URL (or Server URL).

Choose security policy and security mode

Which combinations the server accepts depends on the OPC-UA server's settings:

Minimum transport security
Security policies

SHA-256 policies or stronger

Basic256Sha256, Aes128_Sha256_RsaOaep, Aes256_Sha256_RsaPss

SHA-1 policies or stronger (deprecated)

additionally Basic256 and Basic128Rsa15

None (also offers an unencrypted endpoint)

additionally None

Select Sign & Encrypt as the Security mode. Sign only works when Require Sign & Encrypt is off. The same applies to the None policy with mode None: while Require Sign & Encrypt is on, the server rejects such connections, even though it offers the unencrypted endpoint.

We recommend Basic256Sha256 with Sign & Encrypt.

Log in

  • Username and password: log in as one of the OPC-UA server's users.

  • Anonymous: only possible when Allow anonymous login is on.

The server does not support logging in with a client certificate.

Certificates

The Edge Device creates the server certificate itself on first start. When your client asks whether to trust the server certificate, confirm it. The ENLYZE Platform does not show the certificate's fingerprint yet.

You do not need to install the client certificate on the Edge Device. The server accepts any client's certificate; access is controlled through the login.

Find data in the address space

Under Objects there is one object per data source of the Edge Device, named after the data source. It contains the data source's variables under their display names.

Node
NodeId

Data source

ns=1;g=<UUID of the data source>

Variable

ns=1;g=<UUID of the variable>

NodeIds stay stable as long as the data source and the variable exist. Clients that map data points by NodeId keep their mapping when you rename a display name. You can also get the UUIDs from the Quickstart.

About the values:

  • Each variable shows its most recent value, with its scaling factor applied.

  • If a variable delivers no new value for 10 seconds, its value is empty.

  • The variables are read-only. The server rejects writes with BadNotWritable.

Verify the connection

The connection works when the client lists the Edge Device's data sources under Objects and the variable values update.

Troubleshooting

Problem
Possible cause and fix

No connection, timeout

The client cannot reach the Edge Device. Check the IP address and port, that both are on the same network, and that no firewall blocks the port.

Connecting to 0.0.0.0 fails

The client uses the address from its automatic search. Enter the server URL directly (see above).

Server rejects the connection or login

Security policy or security mode do not match the server's settings, or username and password are wrong.

Data source or variable is missing

The server only shows data sources and variables the Edge Device reads. New variables appear as soon as the Edge Device reads them.

Values are empty

The variable has not delivered a new value for more than 10 seconds. Check the Edge Device's connection to the data source.

Next steps

  • Security: which networks the OPC-UA server is reachable from